Answer to Question #167608 in Electric Circuits for andrew brown

Question #167608

An AC load exhibits a lagging power factor of 0.73 at 230 VAC and 315 amps. If the

system frequency is 60 Hz, calculate the following:


Apparent power (S) =?

A. 72.45 kVA B. 724.5 kVA C. 7.245 kVA


True power (P) =?

A. 5.289 kW B. 52.89 kW C. 528.9 kW


Reactive power (Q) =?

A. 4.952 kVAR B. 495.2 kVAR C. 49.52 kVAR


1
Expert's answer
2021-03-01T11:52:17-0500

"V=230 V\\newline\nI=315A\\newline\nPowerfactor=cos\\phi=0.73\\implies\\phi=43.11\\degree\\newline\\newline\n\n\\newline\n\n1) Apparant \\space power=VI=230\\times315\\newline=72.45kVA"


"2)True\\space power=VIcos\\phi=230\\times315\\times0.73\\newline=52.89kW"

"3) Reactive\\space Power=VIsin\\phi=\\newline230\\times315\\times sin43. 11=49.52kVAR"