A refrigerator is maintained at 4˚C by removing heat from it at a rate of 8 kW. If the required power input to the refrigerator is 2.5 KW, determine (a) the COPR and (b) the rate of heat rejection to the room that houses the refrigerator
Answer is given below:
The food compartment of a refrigerator, is maintained at
4°C by removing heat from it at a rate of 360 kJ/min. If the required power
input to the refrigerator is 2 kW, determine (a) the coefficient of performance
of the refrigerator and (b) the rate of heat rejection to the room that
houses the refrigerator.