20. An air conditioned theater is to be maintained at 80 oF dry bulb temperature and 50% RH(h = 31.35 Btu/lb). The calculated total sensible heat load in the theater is 500,000 Btu/hr, and the latent heat load is 150,000 Btu/hr. The air mixture at 84 oF db and 72 oF wb temperature(h = 35.82 Btu/lb) is cooled to 63 oF dry bulb and 59 oF wet bulb temperature (h = 25.78 Btu/lb)by chilled water cooling coils and delivered as supply air to the theater. Calculate the tons of refrigeration required.
A. 83 B.130 C.127 D.122