A fan delivers 1.75 cu.m/sec of air at a static pressure of 2.5 cm WG through a circular duct with a diameter of 300 mm and discharges it through a 250 - mm diameter duct. If the fan static efficiency is 76%, determine the brake power input to the fan
the brake power input to the fan :
"BHP = \\frac{SP\\times CFM}{6356\\times \\eta_{static}}"
"BHP = \\frac{SP\\times CFM}{6356\\times \\eta_{static}}"
Static Pressure (SP) : 2.5 cm WG
CFM – Cubic Feet Per Minute, is the volume of air moved per minute = 3708.03 cfm
Brake Horsepower, is the horsepower absorbed by the fan:
"BHP = \\frac{2.5 \\times 3708.03}{6356\\times 0.76}= 1.92" W