Answer to Question #230774 in Electrical Engineering for Denie-Pele

Question #230774
A 2000-kVA transformer (A) is connected in parallel with another transformer (B)
rated at 4,000Kva to supply a 3-phase load of 5000kVA at a power factor of 0.8lagging.
Determine the kVA supplied by each transformer, assuming equal no load voltage is applied to
the two transformers. The percentage voltage drops in the windings at their rated loads are as
fellows: Transformer A resistance =2%; reactance =8%
Transformer B resistance =1.6%; reactance =3%
1
Expert's answer
2021-08-30T01:54:30-0400



Given that it’s a 3-phase supply:

KvA supplied by Transformer A:





Using the ratios/percentages




KvA supplied by Transformer A:

kVa= 1300….for (a)

a)

KvA supplied by Transformer B:




kVa supplied by Transformer B:

kVa

kVa= 2400….for (b):