Section 3: (10 marks) Word Problem
Target response size: text portion approximately 1 - 2 paragraphs (or equivalent) of explanation, plus maths portion showing your work
Four electrical devices are connected to powerpoints wired into the same electrical supply circuit. This is a standard Australian residential building circuit rated at 10 A. The devices have power ratings of 200 W, 740 W, 330 W and 1150 W. Can all four devices be operated at the same time on this circuit?
We have given the current rating i.e. 10A
We know Voltage rating in Australia = 230V
For 1st Device,
"P=VI"
"I_1 = \\dfrac{200}{230} = 0.86A"
Similarly for the other three devices current will be
"I_2 = 3.21A"
"I_3=1.43A"
"I_4=5A"
Total current "= 5+1.43+3.21+0.86 = 10.5A"
Hence this value ids greater than the Rated value i.e. "10A."
Hence, all four devices cannot be operated at the same time on this circuit.