An electrical load operates at 120 Vrms . The load as an average of 8 kWbsorb at lagging power factor of 0.8 The effective current 1 rms is
★\bigstar★
Given
120 V rms
8 kW. absorbed power
Power factor i.e Cos(∅)Cos(\varnothing)Cos(∅) =0.8
P=VRMS×IRMS cos(∅)\boxed{P = V_{RMS}\times I_{RMS}\space cos(\varnothing)}P=VRMS×IRMS cos(∅)
⟹ \implies⟹
Irms=8000120×0.8\boxed{I_{rms}= {8000\over 120\times0.8}}Irms=120×0.88000
⟹ Answer\implies Answer⟹Answer
IRMS=83.33A\boxed{ I_{RMS}=83.33 A}IRMS=83.33A