Answer to Question #271844 in Electrical Engineering for Chi

Question #271844

A generator is rated 100 MW, 13.8 kV and 90% power factor. The effective resistance is 1.5 times the ohmic resistance. The ohmic resistance is obtained by connecting two terminals to a DC source. The current and voltage are 88.6 A and 4 V, respectively. What is the effective resistance per phase?





1
Expert's answer
2021-11-29T00:18:05-0500

The answer to your question is provided in the image: