a single phase overhead transmission line delivers 5000 kw at 11 KV and 0.8 factor lagging. total resistance and inductive reactance per conductor is 0.45 ohm and 0.08 ohm respectively , calculate line losses
1
Expert's answer
2021-08-09T05:34:02-0400
"I = \\frac{P}{V_R cos(\\phi_R)} = \\frac{5000\\times 100}{11000\\times 0.8}=568.18A"
Line loss, "I^2R = (568.18^2 \\times 0.45) = 145.27 KW"